testo 922 Heating constructors' Promo set - Heating constructors' Promo set

  • 2-channel measuring instrument with optional radio probe

  • Displays differential temperature

  • Continuous display of max/min values

  • TopSafe, indestructible case, protects from dirt and impact (option)

Heating constructors' Promo set testo 922 incl. testo 922, 2 x pipe wrap probe and transport case

Product Description

testo 922, 2 channel temperature measuring instrument T/C Type K, connection of an optional radio probe, with battery and calibration protocol

testo 922 is a temperature measuring instrument which is especially suited to applications in the HVAC field. The measuring instrument records the temperature values of two connected thermocouple probes, and shows these simultaneously together with the differential temperature in the display. Measurement data transfer by radio additionally allows the measurement value from a further temperature probe to be displayed wirelessly.

With the TopSafe, and the probe plugged in, the measuring instrument has protection class IP65.

The instrument continuously displays the minimum and maximum values. The measurement values shown in the display (current measurement value, fixed measurement value or the minimum/maximum value) can be printed out on site using the Testo report printer (optional). In addiition to this, the measurement values can be cyclically printed – the intervals can be individually set.

 

More Information
Warranty 2 Years
Technical Data
General technical data

Weight

171 g

Dimensions

182 x 64 x 40 mm

Operating temperature

-20 to +50 °C

Product-/housing material

ABS

Number of channels

2-channel

Battery type

9V block battery, 6F22

Battery life

200 h (connected probe, backlight off); 45 h (radio mode, backlight off); 68 h (connected probe, backlight always on); 33 h (radio mode, backlight always on)

Storage temperature

-40 to +70 °C

Temperature - TC Type K (NiCr-Ni)

Measuring range

-50 to +1000 °C

Accuracy

±(0.5 °C + 0.3 % of mv) (-40 to +900 °C)

±(0.7 °C + 0.5 % of mv) (Remaining Range)

±0.1 °C (-50 to +199.9 °C

Resolution

1 °C (Remaining Range)