Fine pressure probe - for heating system checks / 4 pascal measurement

  • Carrying out heating system checks and 4 pascal measurement with compatible flue gas analyzer and accessories

  • Simultaneous measurement of gas pressure and flue gas values

  • No zero point drift during pressure measurement (cyclic zeroing)

fine pressure probe

Product Description

The high-precision probe is used for the measurement of differential pressure and temperature in combination with the testo 320 and testo 330. Heating checks (according to DIN EN 15378) and 4 pascal measurement can be carried out with further accessories.

Cyclic zeroing means the fine pressure probe has no zero point drift and provides high-precision readings. In addition, the fine pressure probe makes simultaneous gas pressure measurement and flue gas analysis possible with the testo 320 or testo 330.

 

Delivery Scope

Fine pressure probe.
More Information
Warranty 2 Years
Technical Data
General technical data

Operating humidity

10 to 90 %RH non-dewing

Operating temperature

5 to +45 °C

Protection class

IP40

Storage temperature

-20 to +50 °C

Temperature - TC Type K (NiCr-Ni)

Measuring range

Depends on probe, max. -40 to +1200 °C

-200 to +300 °C (with surface probe 0604 0994 (accessory))

Accuracy

±0.5 °C (-40 to +100 °C)

±0.5 % of mv (Remaining Range) additionally ±1 digit, additionally accuracy of probe

Resolution

0.1 °C

Measuring rate

max. 1 / s

Differential Pressure - Piezoresistive

Measuring range

-9999.9 to +9999.9 Pa

Accuracy

±0.3 Pa (0 to +9.99 Pa)

±3 % of mv (+10.00 to +9999.9 Pa) additionally ±1 digit

Resolution

0.01 Pa (-149.99 to +149.99 Pa)

0.1 Pa (Remaining Range)

Measuring rate

max. 1 / s

Velocity / Volume flow

Measuring range

Display range: 0.15 to 3 m/s

Resolution

0.1 m/s