Series FDT Flush Diaphragm Transmitter

Flush Diaphragm Transmitter
Non-liquid Filled, ±0.5% F.S.O. Accuracy, SS Wetted Parts

Non-liquid Filled, ±0.5% F.S.O. Accuracy, SS Wetted Parts

The SERIES FDT Flush Diaphragm Transmitter is designed for highly cyclical conditions. Flush sensor feature prevents any potential inaccuracies due to build-up or blockage which is a typical problem found in most non-flush transmitter sensors.

Product Applications

  • OEM
  • Hydraulic systems
  • Process systems
More Information
Model Chart

 

EXAMPLE FDT A 01 NPT Series FDT-A-01-NPT Flush Diaphragm Transmitter, 4-20 mA output, range 100 psi, with 1/4" NPT.
SERIES FDT       Flush Diaphragm Transmitter
OUTPUT   A
V
    4-20 mA
0-5 VDC
RANGE     01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
  100 psi
150 psi
200 psi
300 psi
400 psi
500 psi
600 psi
700 psi
800 psi
900 psi
1,000 psi
2,000 psi
3,000 psi
4,000 psi
5,000 psi
6,000 psi
7.000 psi
8,000 psi
9,000 psi
10,000 psi
OPTIONS       NPT
C08
1/4" NPT
0.25% Accuracy
Service: Compatible liquids and gases, adhesives, slurries, materials that can harden, or where a pressure cavity is not desired.
Wetted Materials: 316 & 15-5 SST.
Accuracy: ±0.5% FS (includes non-linearity, hysteresis, and repeatability).
Stability: ±0.25% FS per year.
Temperature Limits: -40 to 200°F (-40 to 93°C).
Compensated Temperature Limits: 0 to 170°F (-18 to 77°C).
Pressure Limit: 150% FS; Burst: 200% FS.
Thermal Effect: ±1.5% FSO over compensated range.
Power Requirements: 8-38 VDC.
Output Signal: FDT-A: 4-20 mADC; FDT-V: 0-5 VDC.
Response Time: <1 mS.
Loop Resistance:  FDT-A: 0-1.5 ohms; FDT-V: ≤100 ohms.
Electrical Connections: 4 pin.
Process Connection: 7/16-20 UNF male flush diaphragm. Optional 1/4" male NPT.
Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Mount in any position.
Weight: 2 oz (57 g).
Agency Approval: CE.
  • Performs well in high cyclical environments with the presence of water-hammering or spiking for long service life