Series DA-7035N Temperature Switches

Temperature Switches
Bulb and Capillary, Inert Gas Fill

The SERIES DA-7035N Temperature Switches include the same time-proven switching mechanism used in our Series DA pressure switches. Bourdon tube assures high sensitivity and long life. Fully adjustable deadband makes units suitable for a wide range of control applications. Visible, calibrated dial and external adjustments make changing set points simple and fast.

Product Applications

  • Mechanical process temperature monitoring
More Information
Model Chart
EXAMPLE _ _DA_ _ _ _31 _153_ _ _4 Standard DA Bourdon Tube Control, dual setpoint, automatic reset, SPDT mercury switch, 1-35 psig
 
RESET
OPTIONS
        R            U   Manual reset, single adjustment, operates on decrease automatically
G
E
N
E
R
A
L
        R            L   Manual reset, single adjustment, operates on increase automatically
        S(3)       Automatic reset, single adjustment, DS only
        L(1)(3)       Manual lock reset, single adjustment, available as special order only
HOUSING &
APPROVAL
OPTIONS
          W       Weatherproof enclosure, NEMA 3S, 4 and 4X, flanged back standard
N3     W       Weather resistance, includes drain, flanged back standard, available as special order only
          H       Explosion-proof enclosure, control integral, available only on DA, DR, DS
          E       Explosion-proof enclosure, control removable, available on DA, DR, DS
             F       Factory Mutual approval, DAW is FM approved as standard
CIRCUIT
SWITCHING
OPTIONS
    ___2   SPST opens on pressure increase, elect. code A, mercury switch
    ___3   SPST closes on pressure increase, elect. code A, mercury switch
    _153   SPDT, elect. code B, mercury switch
    _156   2 each SPST, one opens as the other one closes, elect. code A, mercury switch
    _804   2 each SPDT, elect. code B, mercury switch, 18" leads, elect. code G, snap switch, screw terminals
    _(___)   Other circuits available, consult factory
  _2 ___2_   SPST opens on increase, elect. code I, DS only, mercury switch
  _2 ___3_   SPST closes on increase, elect. code I, DS only, mercury switch
  _4(2)(8) 4122_   Two stage, includes 2 each SPST, mercury switch
  _4(2)(8) 4129_   Two stage, includes 2 each SPST, mercury switch
  _4(2)(8) 4132_   Two stage, includes 2 each SPST, mercury switch
  _4(2)(8) 4123_   Two stage, includes 2 each SPST, mercury switch
  _5 ___2   SPST mercury switch, elect. code H, opens on increase
  _5 ___3   SPST mercury switch, elect. code H, closes on increase
  70   153   Snap switch, SPDT, elect. code D, 15A @ 120 VAC
  70(12)   804   2 each SPDT, elect. code F, for ranges above 35 psi only, add 30% to minimum deadbands, 702, 703, 704 only
  72   153_   DS only, snap switch, SPDT, elect. code E
  72   804_   2 each SPDT, snap switches, elect. code G, DS only
  74 _____   Two stage, includes 2 each, SPDT snap switches, elect. code G
               B   Delrin Bushed Movement, for all controls
OVERPRESSURE
OPTIONS
  _9 ____2 XX 2500 psi overpressure, 316SS diaph. seal, SPST open on increase, elect. code A, ranges 3,1,4,5S,6S,8S,9S,10S,11S,12S,13S only
  _9 ____3 XX 2500 psi overpressure, 316SS diaph. seal, SPST close on increase, elect. code A, ranges 3,1,4,5S,6S,8S,9S,10S,11S,12S,13S only
  _9 __153 XX 2500 psi overpressure, 316SS diaph. seal, SPDT, elect. code B, ranges 3,1,4,5S,6S,8S,9S,10S,11S,12S,13S only
  92          2_ XX 2500 psi overpressure, 316SS diaph. seal, SPST open on increase, elect. code I, DS only
  92          3_ XX 2500 psi overpressure, 316SS diaph. seal, SPST close on increase, elect. code I, DS only
  95          2_ XX 2500 psi overpressure, 316SS diaph. seal, SPST open on increase, elect. code H
  95          3_ XX 2500 psi overpressure, 316SS diaph. seal, SPST close on increase, elect. code H
RANGES &
BOURDON
TUBE
MATERIALS
      2   25S range 30" Hg vac - 60 psig, type 403SS Bourdon tube
 
      2   26S range 30" Hg vac - 75 psig, type 403SS Bourdon tube
 
      2   5S range 2-60 psig, type 403SS Bourdon tube
 
      2   6S range 5-100 psig, type 403SS Bourdon tube
 
      2   8S range 10-200 psig, type 403SS Bourdon tube
 
      2   9S range 10-300 psig, type 403SS Bourdon tube
 
      2   9AS range 40-350 psig, type 403SS Bourdon tube
 
      2   10S range 25-600 psig, type 403SS Bourdon tube
 
      2   11S range 50-1000 psig, type 403SS Bourdon tube
 
      2   12S range 100-1500 psig, type 403SS Bourdon tube
 
      2   13S range 300-2500 psig, type 403SS Bourdon tube
 
      2   15S range 500-5000 psig, type 403SS Bourdon tube, not avail. with housing E or back conn.
 
      2   16S range 800-8000 psig, type 403SS Bourdon tube, not avail. with housing E or back conn.
 
      3   2 range 0-30" Hg vac, brass Bourdon tube
 
      3   3 range 10" Hg vac - 12 psig, brass Bourdon tube
 
      3   1 range 1/8-15 psig, brass Bourdon tube
 
      3   3A range 1/8-20 psig, brass Bourdon tube
 
      3   4 range 1-35 psig, brass Bourdon tube
 
      3   27 range 25" Hg vac - 50 psig, brass Bourdon tube
 
      3   5 range 2-60 psig, brass Bourdon tube
 
      3   6 range 5-100 psig, brass Bourdon tube
 
      3   7 range 5-150 psig, brass Bourdon tube
 
      3   8 range 10-200 psig, brass Bourdon tube
 
      3   9 range 10-300 psig, brass Bourdon tube
 
      4   26E range 30" Hg vac - 75 psig, 316SS Bourdon tube
 
      4   23E range 5-75 psig, 316SS Bourdon tube
 
      4   6E range 10-100 psig, 316SS Bourdon tube
 
      4   24E range 10-150 psig, 316SS Bourdon tube
 
      4   9E range 10-300 psig, 316SS Bourdon tube
 
      4   21E range 30-400 psig, 316SS Bourdon tube
 
      4   22E range 75-800 psig, 316SS Bourdon tube
 
      4   11E range 100-1000 psig, 316SS Bourdon tube
 
      4   13E range 200-2500 psig, 316SS Bourdon tube
 
      8(6)   23K range 5-75 psig, 316SS Bourdon tube, carbon steel bottom, F housing standard
 
      8(6)   24K range 10-150 psig, 316SS Bourdon tube, carbon steel bottom, F housing standard
 
      8(6)   9K range 10-300 psig, 316SS Bourdon tube, carbon steel bottom, F housing standard
 
CONNECTION &
MOUNTING
OPTIONS
        1     Standard housing
 
        2     Back connection, not available on D-900 series, not available on ranges 15S, 16S
 
        3     Flanged back - standard on "W" models
 
        4     Back connection and flanged back, not available for ranges 15S, 16S, or on D-900, 9200, 9500 series
 
RANGES       35(4)(5)   1N -60 to 30°F, 150°F max., 304 SS bulb and copper capillary std.; SS special order
T
E
M
P
E
R
A
T
U
R
E
 
 
 
 
 
 
 
 
 
 
      35(4)(5)   3N range 0 to 100°F, 240°F max., 304 SS bulb and copper capillary std.; SS special order
      35(4)(5)   4N range 50 to 150°F, 250°F max., 304 SS bulb and copper capillary std.; SS special order
      35(4)(5)   5N range 100 to 200°F, 300°F max., 304 SS bulb and copper capillary std.; SS special order
      35(4)(5)   7N range 140 to 300°F, 500°F max., 304 SS bulb and copper capillary std.; SS special order
      35(4)(5)   8N range 250 to 415°F, 550°F max., 304 SS bulb and capillary std.
      35(4)(5)   9N range 350 to 550°F, 600°F max., 304 SS bulb and capillary std.
      35(4)(5)   10N range 100 to 300°F, 500°F max., 304 SS bulb and copper capillary std.; SS special order
      35(4)(5)   11N range 100 to 500°F, 600°F max., 304 SS bulb and capillary std.
      36(4)(5)(10)   5NS range 100 to 200°F, 300°F max., 304 SS bulb std.
      36(4)(5)(10)   6NS range 140 to 250°F, 380°F max., 304 SS bulb std.
CONNECTION &
MOUNTING OPTIONS
      37(4)(5)(11)     Same as 36 except back connection, 304 SS bulb std.
      38(4)(5)     Same as 36 except has flanged back
      39(4)(5)(9)     Same as 35 except has flanged back and back connection

NOTES: 
(1) Not available on D_ _-_5, 74 or 95.
(2) Available on DA only.
(3) Not available on D_ _ _-70_ _.
(4) & (5) Not available with 9, 92, 95 Diaph. Seals.
(6) Available also as _ _ 28, 58, 708 and 728. Not available with E or H housing or 70-804 circuit.
(7) F available only as DAF, DSF, DRF, DAHF, DRHF, DSHF, not all ranges or circuits.
(8) Switch rating for D-400: AC, 120V @ .3A, 240V @ .15A, 24V @ .8A, DC, 120V @ .15A, 240A @ .07A. Not available for 440V service.
(9) Available only as _ _39, 539, 239, 7039, 7239, 439 and 7439.
(10) Available only as _ _36, 7036 and 7236.
(11) Available only as _ _37, 7037 and 7237.
(12) Available only on 702, 703 and 704.

ELECTRICAL RATING CODES

For Mercury Switch Contacts
CODE
CIRCUIT
SUFFIX NO.
AC CAPACITY
DC RESISTIVE
HORSEPOWER
120V
240V
440V
120V
240V
AC
DC
A
-2, -3
10A
5A
3A
10A
5A
3/4
1/3
B
-153, -804
4A
2A
(1)
4A
2A
1/8
NA
C
-2, -3
(6)
(6)
(6)
10A
5A
3/4
1/3
H
-2, -3
5A
2A
NA
2-1/2A
1A
1/8
1/10
I(2)
-2, -3
0.3A
0.15A
NA
0.15A
0.07A
NA
NA
For Snap-Action Contacts
CODE
CIRCUIT
SUFFIX NO.
AC CAPACITY
DC RESISTIVE
HORSEPOWER
120V
240V
440V
120V
240V
AC
DC
D
-153
15A
15A
15A@480V
1/2A
1/4A
1/8
NA
E
-153
15A
15A
NA
(4)
(4)
(3)
NA
F
-804
12A
10A
5A
1/2A
1/4A
(3)
NA
G
-804
5A
5A
NA
(5)
(5)
NA
NA
 
 
 
 
 
 
 
 
 

 

 

NOTES: 
(1) -153 circuit available 1A 440V AC on special order.
(2) Also rated 0.9A at 24V AC.
(3) 1/4 HP at 120V AC, 1/2 HP at 240V AC.
(4) DC rated controls (up to 10A.
(5) 5A, 30V DC resistive.
(6) 17A non-inductive at 120/240/440V AC.

Service: Compatible liquids or gases.
Wetted Materials: Bulb and connection: 304 SS.
Temperature Limit: Process: See model chart on catalog page; Ambient: 180°F (82°C).
Pressure Limit: 300 psi (20.6 bar).
Enclosure Rating: General purpose. Optional weatherproof and explosion-proof.
Repeatability: ±1% of FS.
Switch Type: SPDT snap switch. Optional DPDT snap and a variety of mercury switches.
Electrical Rating: 10 A @ 120/240/480 VAC.
Electrical Connections: Screw terminal.
Conduit Connection: 7/8" (22.23 mm) hole for 1/2" (12.7 mm) conduit hub.
Process Connection: 3/4" male NPT. Other sizes available.
Mounting Orientation: Vertical and level.
Set Point Adjustment: External knobs for set point and reset point.
Weight: 5 lb (2.3 kg).
Deadband: Adjustable from minimum in model chart to full range. Optional low fixed deadband.
Capillary: 6' (1.8 m) standard. Ranges 1N - 7N, and 10N: copper. Ranges 8N, 9N, 11N: 304 SS.
Set Point Scale: Indication in °F and °C.
Options: See switch type, see enclosures, fixed deadband, longer or shorter capillary, armored capillary, wells, two stage, 1/2" or 1" connection sizes, manual reset.
  • Adjustable deadband
  • Snap action switch standard
  • Inert gas activated Bourdon tube
  • No cross ambient temperature effects
  • No bulb elevation correction required
  • Visible dial calibrated in both °F and °C
  • Visible on/off indication