Model 641B Air Velocity Transmitter

Air Velocity Transmitter
Dirty Air Flow Applications

Dirty Air Flow Applications

The Model 641B Air Velocity Transmitter uses a heated mass flow sensor suitable for dirty air flow applications. It has user-selectable ranges from 250 FPM (1.25 MPS) to 2000 FPM (10 MPS).

Product Applications

  • Exhaust stack flow monitoring
  • Air control in drying processes
  • HVAC air velocity measurements
  • Fan supply and exhaust tracking
  • Clean room ventilation monitoring
Service:Air and compatible, non-combustible gases.
Accuracy:5% FS process gas: 32 to 122°F (0 to 50°C); 6% FS process gas: -40 to 32°F & 122 to 212°F (-40 to 0°C & 50 to 100°C).
Response Time:Flow: 1.5 seconds to 95% of final value (output filter set to minimum).
Temperature Limits:Process: -40 to 176°F (-40 to 80°C). Ambient: 32 to 140°F (0 to 60°C).
Humidity Limit:Non-condensing.
Power Requirements:12 to 35 VDC, 10 to 16 VAC. 1.5 A rating required on supply due to initial power surge drawn by transmitter.
Output Signal:4 to 20 mA, isolated 24 V source, 3 or 4-wire connection.
Output Filter:Selectable 0.5-15 (seconds).
Loop Resistance:600 Ω max.
Current Consumption:300 mA max*.
Electrical Connections:Screw terminal.
Enclosure Rating:Designed to meet NEMA 4X (IP66).
Mounting Orientation:Unit not position sensitive.
Weight:12.6 oz (357.2 g).

*A brief current transient exceeding 300 mA may be seen on startup.

  • SS sensor suitable for dirty air flow measurement
  • Ranges from 250 FPM (1.25 MPS) to 2000 FPM (10 MPS)
  • 4 to 20 mA output
  • Digital filter for signal damping