JavaScript seems to be disabled in your browser. For the best experience on our site, be sure to turn on Javascript in your browser.
Ideally designed for non-invasive checks of insulation condition, the Fluke 360 leakage meter allows you to perform tests without powering down the installation or disconnecting equipment - saving you time, without compromising on quality or safety.
The unique jaw design of the Fluke 360 AC Leakage Current Clamp Meter eliminates the influence of adjacent current conductors, and minimizes the effects of external magnetic fields, even at low currents. This allows you to perform accurate and reliable tests in today’s crowded electrical environments. The tough and high-quality jaw design of the Fluke 360 leakage tester guarantees high stability for long-term repeatability and durability.
Why leakage current testing?Leakage currents can be an indicator of the effectiveness of insulation on conductors. High levels of leakage current may be present in circuits where either the insulation resistance is low, or electronic equipment with filters is used. Leakage currents can cause disruptions of the normal operation of equipment and installations. It is possible to locate the source of leakage currents by using the Fluke 360 leakage current clamp meter and taking methodical measurements throughout the installation. The big advantage of leakage current testing versus insulation testing is that the installation and equipment do not need to be powered down but can be done during normal operation.
AC Current Measurement Specifications (at 23°C ±5°C; 80% R.H. max)
Measurement Range
Resolution
Accuracy
Max. Permissible Current
3mA
0.001mA
±1% of rdg ±5 digits
60 Amps rms
30mA
0.01mA
30A
0.01A
±1% of rdg ±5 digits (0 to 50A)
60A
0.1A
±5% of rdg ±5 digits (0 to 60A)
Mean value detection and rms-value calibration. Accuracy specified at 50/60Hz Frequency range 15Hz to 150Hz
Specifications
Method of Detection
Mean value
Display
Digital display: 3200 counts
Bar-Graph: 32 segment, LCD
Measurement Cycle
Digital display: 2 times/second
Bar-Graph: 12 times/second
Range Switching
Auto Range
Ambient Temperature and Humidity
0°C to 50°C, 80% R.H. or less (no condensation)
Temperature Coefficient
0.05% of range/°C or less (within the range of 0°C to 18°C and 28°C to 50°C for measurement of 0 to 50A)
Influence of External Magnetic Field
0.0005% typical
Influence of Conductor Position
Within accuracy
Circuit Voltage
≤ 300V rms
Withstand Voltage
3.7kV AC for one minute
Safety Specifications
Safety Rating
EN 61010-1, EN 61010-2-032, 300V CAT II, Pollution Degree 2
General Specifications
Jaw Opening
40mm maximum
Power Supply
1 x 3-volt Lithium battery (button cell) CR2032
Battery Life
approx. 90 hours (when continuously used)
Auto Power Off
approx. 10 minutes
Operating Altitude
2000 meters
Dimensions
176mm (L) x 70mm (W) x 25mm (D)
Weight
200g
Ordering Information
Model Name
Description
Fluke 360
Leakage Current Clamp Meter Includes: Soft carrying pouch, and User manual.